The CNC XJ3-D is a protection relay for three-phase 380V AC supplies. It protects against four faults: phase failure, wrong phase sequence, overvoltage and undervoltage. It is used on motors, pumps and other three-phase equipment, because it opens its output contacts when the supply is unsafe.
| Brand | CNC |
| Model | XJ3-D |
| Type | Phase failure, phase sequence, over/undervoltage protection relay |
| Rated Voltage | AC 380V, three-phase |
| Frequency | 50/60 Hz |
| Overvoltage Trip | 380V to 460V, adjustable (delay 1.5 s to 4 s) |
| Undervoltage Trip | 300V to 380V, adjustable (delay 2 s to 9 s) |
| Response Time | 2 s or less |
| Contacts | 1 changeover (Ta, Tb, Tc) |
| Contact Rating | AC-15, 380V / 0.47A; thermal current 3A |
| Electrical Life | 100,000 operations |
| Mechanical Life | 1,000,000 operations |
| Mounting | 35 mm DIN rail or screw mounting, upright |
| Operating Temperature | -5°C to +40°C |
Setup note: Set the overvoltage knob slightly below your equipment's maximum voltage and the undervoltage knob slightly above its minimum. If the motor does not start and the phase failure light is on, swap two phases and try again.
Protection for three-phase motors, water pumps, compressors, and control panels where a missing phase, reversed rotation or unsafe voltage could damage equipment.
Available from Sultani Solar, Sialkot.